Honeywell VRX180 User Manual
Page 139

Programming Function Blocks and Features
Video Recorder – User Manual
125
Interval Timer
This timer counts down from the preset value in minutes. This time remaining is CVn OV. The timer
has a single discrete output CVn OS which is ON(1) while the timer is actively counting or while RESET
is ON(1), and OFF(0) while the timer has timed out to zero. When RESET/RUN switches ON(1) the
timer resets to the preset value; an ON(1) to OFF(0) transition starts the timer.
Table 4-34 describes the Interval Timer prompts. See Table 4-2 for additional prompts.
Table 4-34 Interval Timer Prompts
Prompt
Range/Selections
Definition
PRESET
OFF, analog parameter,
number
Timer counts to zero from this number of minutes.
RESET/RUN
OFF, discrete parameter, 0, 1
Controls the operation of the timer.
RANGE LOW
RANGE HIGH
OFF or number
Enter the output’s display limits. Output is not clamped or
flashed when it exceeds these limits.