Start-Up Operation

Multiple Systems With Multiple

Evaporators (Requires A Smart

Controller)

• Check all wiring connections to be sure

they are correct and tight.

• On the condensing units

-

Check setting of time delay relay.

It should be set at 1 minute

(the second marker).

-

Check the low pressure switch setting on

freezer units. Refer to H-IM-CU.On some

condensing units, the low pressure switch

has a fixed setting and cannot be adjusted.

• Turn power on.

• On the MASTER evaporator

-

DO NOT REMOVE the room sensor

from any evaporator

S

S

S

M

CU

S

S

S

M

CU

S

S

S

M

CU

M

S

S

S

CU

SMART

CONTROLLER

SYSTEM 1

SYSTEM 2

SYSTEM 3

SYSTEM 4

M = Master Evaporator

S = Slave Evaporator

CU = Condensing Unit

MULTIPLE SYSTEM CONNECTION

(See Smart Controller instruction manual for more details)

• On the SLAVE evaporators.

All Beacon II boards are shipped with the factory

default as a “MASTER” evaporator.

- Each SLAVE evaporator must be

changed to identify it as a SLAVE.

Use the “

PROGRAM REVIEW

button to scroll until

SLA appears,

then use the “

SELECT” knob to

select

YES then press “ENTER.”

• Use the Beacon II Smart Controller to

set system parameters. See Beacon

II Smart Controller installation

instructions for more details.