beautypg.com

Programming & reviewing – Heatcraft Refrigeration Products BEACON II H-IM-79E User Manual

Page 13

background image

13

Programming & Reviewing

FORCE

DEFROST

RESET

TIME

MONITOR

FORCE

SERVICE

Use the “MONITOR”

button to review these items:

SUP - Superheat

(°F/°C)

ESP - Expansion valve steps

(0 to 255 steps)

SCt - Suction temperature

(°F/°C)

SSt - Saturated Suction temperature

(°F/°C)

SCP - Suction pressure at Evaporator

(PSIG/HG)

Odt - Outdoor temperature

(°F/°C)

dFt - Defrost sensor temperature

(°F/°C)

dFS - Time left until next defrost

(hours) (on version 1.8 boards)

dFE - Last Defrost Elapsed time

(minutes)

AC

- Board Voltage

SPt - Spare Temperature reading

rEL

- Software release program

Use this button to

“FORCE DEFROST”. To force a

defrost , press the

“FORCE DEFROST” button. The

system will pumpdown and shut off the compressor. The
heaters are then turned on. The display will show

dEF

and room temp.

Use this button to

“RESET TIME”. Pressing this button

will reset the time clock in the microprocessor to zero.
At initial power up, pressing this button will bypass
the “four minute” hold-off and the system will start
immediately after the expansion valve opens. This
display will show

dLy.

Use this button to

“FORCE SERVICE”. Pressing this

button TWICE will cause the system to pumpdown
and the compressor to shut off. The system will
remain off until the “

CLEAR” button is pressed. While

in the “

FORCE SERVICE”, the LED display will only

show

SEr.