beautypg.com

Installation, Installation tips, Condensing unit – Heatcraft Refrigeration Products BEACON II H-IM-79E User Manual

Page 3: Evaporator unit

background image

3

Installation Tips

• Use a minimum 18 gauge wire for all low

voltage connections


• The Beacon II board gets its 24 VAC power

supply from a transformer mounted in the

electrical end of each evaporator. On

208-240 volt systems, the multi-tap

transformer is shipped from our factory wired

for 240 volts. If your supply voltage is 208

volt, you must change to the 208 volt tap on

the transformer.


NOTE: On multiple evaporators, since a

transformer is in each evaporator, the

voltage tap must be set on each

evaporator.


• Refer to wiring schematic shipped on units

for unit wiring. Schematics in this Installation

& Operation Manual are typical wiring

schematics only.

• Program ALL slave evaporators as SLAVES.


• Evaporators are shipped from our factory

with a preset box setpoint temperature of

35°F for air defrost and -10°F for electric

defrost. If your box setpoint temperature

requirements are different, this must be set

using directions outlined under “Room

Temperature Control”.

• The suction line temperature sensor MUST

be removed from the suction line before

brazing the suction tubing. The sensor

MUST then be reinstalled on the suction

line after brazing is completed and the tubing

has cooled. Insulate when finished.

• The low pressure switch time delay relay,

located in the condensing unit, must be set

to 1 minute.

• If electrical power will be connected prior to

evacuation and charging of system, unplug

electric expansion valve from board until

system is ready to be evacuated, leak tested

and charged.

• There are built-in ground connections on the

Beacon II’s four corner brass spacers. Use four

sheet-metal screws to mount the board on the

Installation

evaporator for common-mode noise filtering.

Make sure that the evaporator ground terminal

is earth grounded.

• Some systems may require the crankcase

heater be energized 24 hours prior to

start-up. The Beacon should be de-

energized for this period by placing it in

the

SERVICE MODE. This is done by

pressing the

FORCE SERVICE button

twice. To start the system cooling, press the

CLEAR button.

• Room sensors may be left connected on

ALL evaporators. Room sensors must be

connected on master.

• A pressure transducer is installed on the

evaporator. Do not leak test system above

150 PSI or damage to transducer could

occur. If leak testing must be greater than

150 psig, disconnect the transducer from

the suction header and reconnect after

testing is complete.

Condensing Unit

The condensing unit control panel contains the relays,
contactors, time delay and a terminal block which is
appropriately marked to match the low voltage wiring
connections. A sensor for outdoor air temperature
measurement is installed on the condensing unit.

Condensing unit must be installed using proper
refrigeration practices and codes. Make sure there is
sufficient clearances around unit for adequate air flow
and access.

Evaporator Unit

The evaporator contains the Beacon II controller, electric
expansion valve, pressure transducer, distributor, orifice,
transformer and three sensors. These components are
all factory mounted and wired. The three sensors are
factory mounted and provide input to the controller from
the following: defrost temperature, suction temperature,
room temperature

Each evaporator unit must be installed using proper
refrigeration practices and codes. Make sure the
piping is correctly sized and properly routed. It is highly
recommended that the liquid and suction lines be
insulated. There must also be good clearance around
unit. See H-IM-UC Installation and Operation manual for
more details.