Programming & reviewing – Heatcraft Refrigeration Products BEACON II H-IM-79E User Manual

Page 12

background image

12

• Defrost Type –

A-E” - Selection is made for air

defrost or electric defrost coil. This will

automatically set the system factory defaults for

air defrost and electric defrost. (See default

settings.)

• Refrigerant Type -

rEF- Selection for type of

refrigerant - R-22, R-404A or R-507. Default:

Air defrost is R-22 and for electric defrost it is

R-404A.

• Box Temperature -

bot- Select box temperature

setpoint. Selection range is -30°F to +70° F.

Defaults: Electric defrost -10°F and air defrost

+35°F.

• Superheat -

SUP” - Evaporator superheat is

controlled by the board on each evaporator.

Each board measures the evaporator saturation

suction temperature and the suction pressure to

determine the superheat. The superheat value

at the evaporator can be changed to ensure a

20°F to 30°F superheat at the Compressor.

Default: 8°F.

• Evaporator Board: Slave? -

SLA - On multiple

evaporator systems, each evaporator board has

to be programmed to be a Master or a Slave.

Each board is shipped from our factory set as

a Master. You must make this change to each

Slave evaporator. A selection of “YES” is made

for this setting.

The default for each board is a Master, so on

Single Evaporator systems no change is

required.

• Number. of Defrost per Day - “dFn

” - A selection

must be made for the number of defrosts cycles

per day – 1,2,3,4,5,6,8,10 or 12 per day. If no

selection is made, defaults: electric defrost 4 per

day and air defrost 2 per day.

Programming & Reviewing

Programming And Reviewing Settings / Changes (cont’d.)

Use the

“PROGRAM REVIEW” button to select these items:

• Defrost fail-safe -

dFF- This is the maximum

time allowed for a coil to remain in defrost.

Defrost will be terminated if the defrost end

temperature is not attained when this time

has expired. On multiple evaporator systems, this

is controlled by the Master unit. Each board

should have the same setting. Defaults: electric

defrost 30 minutes and air defrost 40 minutes.

• Defrost End Temperature - “dFt

- This is the

temperature at which the defrost will be

terminated. Defaults: electric defrost +60°F and

air Defrost +45°F.

• Defrost Delay Start Time -

dFS - This allows

the delay of the start of the first defrost. Default:

0.0 hours.

• Alarm High Temperature - “ALH

- Temperature

at which a high box temperature alarm will be

triggered. This does not apply during defrost.

Defaults: electric defrost +5°F and air defrost

+50°F.

• Alarm Low Temperature -

ALL- Temperature

at which a Low Box Temperature alarm will be

triggered. Defaults: Electric Defrost -15°F and Air

Defrost +30°F.

• Alarm Time -

ALt- Time which High

Temperature or Low Temperature condition must

exceed before alarm is triggered. Default:

60 minutes.

• °F/°C -

F-C- Select units to display

temperature. Fahrenheit or Celsius. Default:

Fahrenheit. When °C is selected a red dot will

appear in the right bottom corner of the LED

display of the Beacon II board.