Single System With Multiple

Evaporators

• Check all wiring connections to be sure

they are correct and tight.

• On the condensing unit

- Check the setting of time delay relay. It

should be set at 1 minute (the second

marker).

- Check the low pressure switch setting on

freezer units. Refer to H-IM-CU. On some

condensing units, the low pressure switch

has a fixed setting and cannot be adjusted.

• Turn power on.

• On the MASTER evaporator

- DO NOT REMOVE the room sensor

- Use the “

PROGRAM REVIEW” button

to scroll through settings.

- Check “rEF” (Refrigerant Type).

Factory defaults are: air defrost

R-22, electric defrost R-404A.

Change to the refrigerant being used.

M = Master Evaporator

S = Slave Evaporator

CU = Condensing Unit

CU

M

S

S

S

Start-Up Operation

- Check

bot (Box Temperature).

Factory defaults are: air defrost

35°F and electric defrost –10°F.

Change to the desired temperature.

- Review and change other setting if

necessary.

- See procedures on page 12 on how to

change settings.


• On the SLAVE evaporators.

All Beacon II boards are shipped with the factory

default as a “MASTER” evaporator.

- DO NOT NEED TO REMOVE the Room

Sensor on any evaporator

- Each SLAVE Evaporator must be

changed to identify it as a SLAVE.

Use the “

PROGRAM REVIEW” button

to scroll until

SLA appears, then

use the “SELECT” knob to select

“YES” then press “ENTER.”