beautypg.com

Installation, Power supply, Wiring – Heatcraft Refrigeration Products BEACON II H-IM-79E User Manual

Page 4: Refrigerant line brazing (caution)

background image

4

The electric expansion valve and the suction temperature
sensor on the suction line are factory installed.Care must
be taken when brazing these lines at the evaporator.

Too high a temperature may destroy these

components. Heat absorbing compounds or “wet

rags” must be used to protect the electric expansion

valve when brazing the refrigerant line connections.

The suction line sensor should be removed before

brazing.

Power Supply

The Beacon II board gets its 24 VAC power supply from
a transformer mounted in the electrical end of each
evaporator. On 208-240 volt systems, the multi-tap
transformer is shipped from our factory wired for 240
volts. If your supply voltage is 208 volt, you must change
to the 208 volt tap on the transformer.

VERY IMPORTANT: If the supply voltage to the

evaporator is 208 volts, the primary tap of the
transformer must be moved to the 208 volt tap.

This must be done for all the evaporators on that

system.

If the 24 VAC power supply falls below 18 VAC the
system may power down and shut off. When the power
supply is corrected to 24 VAC the system will restart
after the four minute hold-off period and resume normal
operation.

On Beacon II systems,the main power for the evaporator
can be supplied separately from the power supply of the
condensing unit. All wiring, however, must comply with
local electrical codes.

Wiring

Wiring between the condensing unit and the unit
cooler(s) will be as follows (see wiring diagrams):

• High voltage - There may be high voltage on

the defrost heater relay and the fan relay.

The evaporator may also be connected to a

separate power supply from the condensing

unit. See unit cooler spec. plate for ampacity.

Installation

• Low voltage - 24V Class II control circuit.

A total of five low voltage leads are required

to connect the condensing unit to the

evaporator. (See wiring diagram.) Two of

these leads are for connecting the outdoor

temperature sensor. The other three leads

are for connecting the compressor contactor

service switch and 24V Common inputs.

All 24 volt wiring must be run separate

from the line voltage wiring.

• Low voltage wiring must be 18 gauge

minimum. For low voltage wiring, maximum

distances are:

Condensing unit to Master evaporator

500 ft.

Between evaporators

500 ft.

Smart Controller to Master evaporator

1000 ft.

• Multiple units – The multi-in and multi-out

are the communication connections.

Connection sequence must follow the multi-

out terminal to the multi-in terminal and

the multi-out back to the multi-in terminal in

a daisy chain loop.

• Alarm circuit - The onboard alarm is a dry set

of NC contacts which closes to indicate an

alarm or loss of power. The type and wiring for

the alarm is customer specified. Note that the

alarm circuit does not distinguish or indicate

what has caused the alarm.

• All wiring must comply with all applicable

codes and ordinances.

Refrigerant Line Brazing (Caution)