Each Beacon II board power is supplied by a transformer in the evaporator on which

it is mounted. Do not run any 24 VAC wires between Beacon II boards on the evaporators.

Configuration

CU

M

S

S

S

M = Master Evaporator

S = Slave Evaporator

CU = Condensing Unit

If there are multiple evaporators on a system, the
program for each SLAVE evaporator must be changed to
identify it as a SLAVE. To do so, press the “

PROGRAM

REVIEW” button repeatedly until “SLA” appears then use

the “

SELECT” knob to select “YES” and press “ENTER”.

All Beacon II boards are shipped with the factory

default as a MASTER evaporator. Place all boards in the

SERVICE” mode while you program the setpoints to

avoid errors and alarms which may cause troubles at
startup.

VERY IMPORTANT: This must be done for each slave

board.

Multiple Evaporator Configuration (Master/slave)

Up to 4 evaporators can be connected as a
master/slave configuration.

DO NOT remove the room

sensor from any of the Beacon II boards.

This also applies when connected to the optional Smart
Controller.

PROGRAM

REVIEW

SELECT