0 battery run times, Attery, Imes – Emerson Liebert UPStation GXT2U User Manual
Page 37
Battery Run Times
33
13.0 B
ATTERY
R
UN
T
IMES
Load% 700VA 1000VA 1500VA 2000VA 3000VA
Internal
Battery
(minutes)
10%
248
191
144
56
91
20%
115
87
53
33
46
30%
79
48
38
26
30
40%
58
34
28
19
21
50%
44
25
20
14
16
60%
35
19
15
12
11
70%
29
16
12
10
9
80%
24
13
10
8
8
90%
20
12
8
7
7
100%
17
11
7
6
5
Internal Battery
+ 1 External
Battery Cabinet
(minutes)
10%
992
764
576
328
364
20%
460
348
212
159
184
30%
316
192
152
88
120
40%
232
136
112
67
84
50%
176
100
80
52
64
60%
140
76
60
36
44
70%
116
64
48
30
36
80%
96
52
40
24
32
90%
80
48
32
21
28
100%
68
44
28
18
20
Internal Battery
+ 2 External
Battery
Cabinets
(minutes)
10%
1984
1528
1152
392
728
20%
920
696
424
231
368
30%
632
384
304
182
240
40%
464
272
224
133
168
50%
352
200
160
98
128
60%
280
152
120
84
88
70%
232
128
96
70
72
80%
192
104
80
56
64
90%
160
96
64
49
56
100%
136
88
56
42
40
Internal Battery
+ 3 External
Battery
Cabinets
(minutes)
10%
2976
2292
1728
560
1092
20%
1380
1044
636
330
552
30%
948
576
456
260
360
40%
696
408
336
190
252
50%
528
300
240
140
192
60%
420
228
180
120
132
70%
348
192
144
100
108
80%
288
156
120
80
96
90%
240
144
96
70
84
100%
204
132
84
60
60
Internal Battery
+ 4 External
Battery
Cabinets
(minutes)
10%
3968
3056
2304
840
1456
20%
1840
1392
848
495
736
30%
1264
768
608
390
480
40%
928
544
448
285
336
50%
704
400
320
210
256
60%
560
304
240
180
176
70%
464
256
192
150
144
80%
384
208
160
120
128
90%
320
192
128
105
112
100%
272
176
112
90
80
Note: Approximate discharge times are in minutes and at 25°C (77°F) with a 100% resistive load.