Battery Run Times

33

13.0 B

ATTERY

R

UN

T

IMES

Load% 700VA 1000VA 1500VA 2000VA 3000VA

Internal

Battery

(minutes)

10%

248

191

144

56

91

20%

115

87

53

33

46

30%

79

48

38

26

30

40%

58

34

28

19

21

50%

44

25

20

14

16

60%

35

19

15

12

11

70%

29

16

12

10

9

80%

24

13

10

8

8

90%

20

12

8

7

7

100%

17

11

7

6

5

Internal Battery

+ 1 External

Battery Cabinet

(minutes)

10%

992

764

576

328

364

20%

460

348

212

159

184

30%

316

192

152

88

120

40%

232

136

112

67

84

50%

176

100

80

52

64

60%

140

76

60

36

44

70%

116

64

48

30

36

80%

96

52

40

24

32

90%

80

48

32

21

28

100%

68

44

28

18

20

Internal Battery

+ 2 External

Battery

Cabinets

(minutes)

10%

1984

1528

1152

392

728

20%

920

696

424

231

368

30%

632

384

304

182

240

40%

464

272

224

133

168

50%

352

200

160

98

128

60%

280

152

120

84

88

70%

232

128

96

70

72

80%

192

104

80

56

64

90%

160

96

64

49

56

100%

136

88

56

42

40

Internal Battery

+ 3 External

Battery

Cabinets

(minutes)

10%

2976

2292

1728

560

1092

20%

1380

1044

636

330

552

30%

948

576

456

260

360

40%

696

408

336

190

252

50%

528

300

240

140

192

60%

420

228

180

120

132

70%

348

192

144

100

108

80%

288

156

120

80

96

90%

240

144

96

70

84

100%

204

132

84

60

60

Internal Battery

+ 4 External

Battery

Cabinets

(minutes)

10%

3968

3056

2304

840

1456

20%

1840

1392

848

495

736

30%

1264

768

608

390

480

40%

928

544

448

285

336

50%

704

400

320

210

256

60%

560

304

240

180

176

70%

464

256

192

150

144

80%

384

208

160

120

128

90%

320

192

128

105

112

100%

272

176

112

90

80

Note: Approximate discharge times are in minutes and at 25°C (77°F) with a 100% resistive load.