Controls and Indicators

14

6.0

C

ONTROLS

AND

I

NDICATORS

6.1

ON/Alarm Silence/Manual Battery Test Button

This button controls output power to connected load(s) and has

three functions:
• ON
• Alarm Silence
• Manual Battery Test

ON - Pressing this button will start up the UPS in order to provide

conditioned and protected power.
Alarm Silence - To silence alarms, press this button for at least one

second. After the alarm is silenced, the Liebert UPStation GXT2U will

reactivate the alarm system to alert of additional problems.

Manual Battery Test - To initiate a manual battery test, press the

ON button for at least one second while operating from mains power

with no alarm conditions present.

• If only three of the five Battery LEDs illuminate, allow the UPS to

recharge the batteries for 24 hours.

• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five Bat-

tery LEDs illuminate, contact your local dealer, Liebert represen-

tative or Liebert Worldwide Support Group.

NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT

be silenced.

All LEDs illuminated

for illustrative purposes only.