Major Components

6

4.4

Battery Charger

The battery charger utilizes energy from the mains power and pre-

cisely regulates it to continuously “float charge” the batteries. The bat-

teries are being charged whenever the Liebert UPStation GXT2U is

plugged in, even when the UPS is not turned on.

4.5

DC to DC Converter

The DC to DC converter utilizes energy from the battery system and

raises the DC voltage to the optimum operating voltage for the

inverter. This allows the inverter to operate continuously at its opti-

mum efficiency and voltage, thus increasing reliability.

4.6

Battery

The Liebert UPStation GXT2U utilizes valve-regulated, nonspillable,

lead acid batteries. To maintain battery design life, operate the UPS

in an ambient temperature of 20°C to 25°C (68°F to 77°F). Optional

external battery cabinets are available to extend battery run times.

4.7

Dynamic Bypass

The Liebert UPStation GXT2U provides an alternate path for mains

power to the connected load in the unlikely event of a UPS malfunc-

tion. Should the UPS have an overload, overtemperature, or UPS fail-

ure condition, the UPS automatically transfers the connected load to

bypass. Bypass operation is indicated by an audible alarm and illumi-

nated amber Bypass LED (other LEDs may be illuminated to indicate

the diagnosed problem). To manually transfer the connected load from

the inverter to bypass, press the Standby button once.

NOTE
The bypass power path does NOT protect the connected

equipment from disturbances on the mains supply.