Controls and Indicators

16

6.7

Battery Indicator LED (Amber)

The Battery indicator LED is illuminated when the UPS is operating

on battery.

6.8

AC Input Indicator LED (Green)

The AC Input indicator LED is illuminated when mains power is

available and within the input specifications.

6.9

Output Voltage Selection

The Output Voltage is user configurable and is designed to allow

selecting or changing the desired output voltage to match the mains

via the Liebert UPStation GXT2U Configuration Program provided

with the UPS. The settings to choose from are 200, 208, 220, 230, and

240 VAC output. The factory default setting is 230 VAC.

!

CAUTION

Never change the voltage settings while the UPS is ON and

powering connected loads.

NOTE
Setting output voltage to 200 VAC will cause the UPS unit to

be derated (700/1000 VA to 90%, 1500/2000/3000 VA to 80%)

of the VA and watt ratings listed in 12.0 - Specifications.