0 specifications, Pecifications – Emerson Liebert UPStation GXT2U User Manual
Page 34
Specifications
30
12.0 S
PECIFICATIONS
Model Number
GXT2-700RT230
GXT2-1000RT230
GXT2-1500RT230
Model Rating
700VA / 490W
1000VA / 700W
1500VA / 1050W
DIMENSIONS: mm
Unit W x D x H: mm
87 x 547 x 430
87 x 547 x 430
87 x 547 x 430
Shipping W x D x H: mm
268 x 692 x 585
268 x 692 x 585
268 x 692 x 585
WEIGHT: kg
Unit: kg
22.5
22.6
23.2
Shipping: kg
26.5
26.6
27.2
INPUT AC PARAMETERS
Voltage Range
(typical)
230 VAC nominal;
variable based on output load
100% - 90% loading 159VAC / 280VAC
159VAC / 280VAC
176VAC / 280VAC
90% -70% loading 159VAC / 280VAC
159VAC / 280VAC
159VAC / 280VAC
70% -30% loading 139VAC / 280VAC
139VAC / 280VAC
139VAC / 280VAC
30% - 0% loading 119VAC / 280VAC
119VAC / 280VAC
119VAC / 280VAC
Frequency
40 - 70 Hz; Auto Sensing
Input Connector
IEC320-10A
OUTPUT AC PARAMETERS
Output Sockets
(6) EN 60320/C13
Voltage
200/208/220/230/240 (user configurable) VAC; ±3%
Frequency
50 Hz or 60 Hz
Waveform
Sinewave
Main Mode
Overload
200% for 8 cycles;
130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
Qty x V x Rating
4 x 12V x 7.0 or 7.2 AH
Battery Mfg/Part #
China Storage Battery / CSB 1270 F2
Back-up Time
Recharge Time
5 Hours to 95% capacity after full discharge
into 100% load (Internal Batteries Only)
ENVIRONMENTAL
Operating Temp
0°C to +40°C (+32°F to +104°F)
Storage Temp
-15°C to +50°C (+5°F to +122°F)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 3000 m (10,000 ft.) at 40°C (104°F) without derating
Storage Elevation
15,000 m (50,000 ft.) maximum
Audible Noise
<50 dBA, at 1 metre from the rear
<45 dBA, at 1 metre from the front or sides
AGENCY
Safety
EN 62040-1, CE compliance mark,
for both Low Voltage and EMC Directives
RFI/EMI
EN 62040-2, Class B
Surge Immunity
EN 61000 4-2, 4-3, 4-4, 4-5
Transportation
ISTA Procedure 1A