Installation

10

3. Determine the height position inside the rack enclosure where you

want to mount the UPS or battery cabinet.

Install rear member of each

bracket assembly into rack

enclosure with two (2) M5

screws provided in this kit.

(See figure at right.) Return

flanges on bracket assembly

fit to the inside of rack

mounting rails. Insert

screws loosely (finger-tight)

into top and bottom holes of

return flange on rear mem-

ber. Extend bracket assem-

bly by sliding front member

forward until it touches the front rack mounting rail. Insert two (2)

M5 screws loosely (finger-tight) into top and bottom holes of return

flange on each front member. Make sure bracket assemblies are at

the same mounting height on all four (4) rack mounting rails.

4. Locate eight (8) M4 screws and eight (8) M4 nuts from hardware

pack in this kit. Each nut has a locking, nylon insert that begins

gripping the screw when it is halfway tight. Make sure to tighten

nut and screw completely to assure locking action. Fasten rear

member and front member together using four (4) screws and four

(4) nuts per bracket assembly as shown in the figures below. For

maximum support, locate fasteners for each bracket assembly as

far apart as possible, depending on rack depth, while still joining

both members (See figures below). Check alignment of bracket

assemblies and TIGHTEN ALL SCREWS FROM Steps 3 and 4.

!

CAUTION

Reduce risk of tipping the rack enclosure by placing UPS or

battery cabinet in the lowest possible rack position.

M5 screws

M5 screws

Front rack

mounting rails

Rear rack

mounting

rails

32" rack

depth

M4 nuts

M4 nuts

M4

screws

18" rack

depth

M4 nuts

M4 nuts

M4

screws