1 led status indicators, 1 ethernet led indicators, Led status indicators – ProSoft Technology PTQ-104C User Manual
Page 94: Ethernet led indicators, Led indicators
Diagnostics and Troubleshooting
49TPTQ-104C ♦ 48TQuantum Platform
12TUser Manual
47TIEC 60870-5-104 Client
8.1
LED Status Indicators
LED
Color
Status
Description
PRT1
Green
On
Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.
Off
No data is being transferred on the Configuration/Debug port.
PRT2
Green
On
Port not used in application
Off
Port not used in application
PRT3
Green
On
Port not used in application
Off
Port not used in application
ERR1
Red
Off
The PTQ-104C is working normally.
On
The PTQ-104C module program has recognized an application
error.
ERR2
N/A
Not used in application
ERR3
Red
On
Configuration Error
Active
Green
On
The LED is on when the module recognizes a processor and is
able to communicate if the [Backplane Data Movement] section
specifies data transfer commands.
Off
The LED is off when the module is unable to communicate with the
processor. The processor either absent or not running.
BAT
Red
Off
The battery voltage is OK and functioning.
On
The battery voltage is low or the battery is not present. The battery
LED will illuminate briefly upon the first installation of the module or
if the unit has been un-powered for an extended period of time.
This behavior is normal, however should the LED come on in a
working installation please contact ProSoft Technology.
If the module is not operating and the status LEDs are not illustrated in the table
above, please call ProSoft Technology for technical assistance.
8.1.1 Ethernet LED Indicators
LED
State
Description
Data
Off
No activity on the Ethernet port.
Green Flash
The Ethernet port is actively transmitting or receiving data.
Link
Off
No physical network connection is detected. No Ethernet
communication is possible. Check wiring and cables.
Green Solid
Physical network connection detected. This LED must be on
solid for Ethernet communication to be possible.
Page 94 of 136
ProSoft Technology, Inc.
March 4, 2013