Module Configuration
49TPTQ-104C ♦ 48TQuantum Platform
12TUser Manual
47TIEC 60870-5-104 Client
ACTTERM with
setpoint
Y or N
This parameter specifies what the last message
will be in the response to a setpoint command. If
the parameter is set to Y, an ACTTERM will be
the last response. If set to N, ACTCON will be the
last response.
Status Offset
-1 to 3956
-1: Disable
0-3956: Database location of client status data
NOTE: requires 44 registers and should be placed
in a location of the module memory that is being
used for read data to transfer this information
back to the processor.
5.6.2 [IEC-104 Client/Session x > IEC-104 Client x Sector 0] section
Item
Range
Description
Common ASDU
Address
0 to 65535
This parameter sets the common ASDU address
to associate with this sector of the specified
session.
Online Time Sync
Y or N
This parameter specifies if the sector in the
controlled device will be sent a time
synchronization command when the unit is first
recognized as being online.
Online General Int
Y or N
This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command when the unit is first
recognized as being online.
EOI Time Sync
Y or N
This parameter specifies if the sector in the
controlled device will be sent a time
synchronization command after this module
receives an EOI message from the controlled unit.