Iec 60870-5-104 client specifications, Hot standby – ProSoft Technology PTQ-104C User Manual
Page 108

Reference
49TPTQ-104C ♦ 48TQuantum Platform
12TUser Manual
47TIEC 60870-5-104 Client
Database Type
Description
Event Generation Point Size
M_DP_NA
Monitored dual-point database
State Change
2 bits
M_ST_NA
Monitored step-point database
State Change
1 byte
M_BO_NA
Monitored Bitstring database
Dead-band
2 wprds
M_ME_NA
Monitored normalized-point database
Dead-band
1 word
M_ME_NB
Monitored scaled-point database
Dead-band
1 word
M_ME_NC
Monitored short-float point database
Dead-band
2 words
M_IT_NA
Monitored integrated total database
N/A
2 words
C_SC_NA
Command single-point database
N/A
1 bit
C_DC_NA
Command dual-point database
N/A
2 bit
C_RC_NA
Command step-point database
N/A
1 byte
C_SE_NA
Command normalized-point database
N/A
1 word
C_SE_NB
Command scaled-point database
N/A
1 word
C_SE_NC
Command short-float point database
N/A
2 words
C_BO_NA
Command 32-bit Bitstring database
N/A
2 words
IEC 60870-5-104 Client Specifications
The IEC 60870-5-104 Client functionality supported by the module includes:
The IEC 60870-5-104 communication driver is built in accordance to the
approved IEC specification
The module functions as a Client on the network supporting data read/write
commands to IEC 60870-5-104 servers on the network
Four TCP sockets
Supports clock synchronization commands from client or from the Quantum
Supports Group interrogation and Counter interrogation commands.
Optional user defined list of acceptable client host IP addresses
Configurable Common ASDU address (sector) and Information Object
Address
An IEC Interoperability Document for the ProTalk is available which fully
documents data types supported by the module
Hot Standby
Hot Standby features support the SE 140 671 CPU
Supports up to six PTQ-104C Hot Standby modules per rack
Module automatically detects Hot Standby system
Page 108 of 136
ProSoft Technology, Inc.
March 4, 2013