ProSoft Technology PTQ-104C User Manual
Page 67
49TPTQ-104C ♦ 48TQuantum Platform
Module Configuration
47TIEC 60870-5-104 Client
12TUser Manual
Item
Range
Description
EOI Time Sync
Y or N
This parameter specifies if the sector in the
controlled device will be sent a time
synchronization command after this module
receives an EOI message from the controlled unit.
EOI General Int
Y or N
This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command after this module receives
an EOI message from the controlled unit.
Use Time Tag
Commands
Y or N
This parameter specifies if a time tag field is to be
included with commands. This is as specified in
the IEC-870-5-104 specification and should only
be utilized if the controlled device supports these
new data types. If the parameter is set to Y, a time
tag will be added to all commands. If the
parameter is set to N, the normal IEC-870-5-101
data type messages will be utilized
5.6.5 [IEC-104 Client/Session x > IEC-104 Client x Sector 1] section
This section defines the Data Type distribution of the module database for Client
x Sector 1.
ProSoft Technology, Inc.