ProSoft Technology PTQ-104C User Manual
Page 63

49TPTQ-104C ♦ 48TQuantum Platform
Module Configuration
47TIEC 60870-5-104 Client
12TUser Manual
5.6.1 [IEC-104 Client/Session x > IEC-104 Client x] section
Item
Range
Description
Server IP Address
IP dotted
notation
IP address for the server to connect this client to
with 0.0.0.0 used to disable the client.
Sector Count
1 or 2
This parameter sets the number of sectors
contained in this controlled device. The range of
values is from 1 to 2. A sector section is required
for each sector in a session to define its database
and settings.
T0 timeout
1 to 30
Number of seconds to wait for connection to be
established with server in seconds (default=30)
T1 timeout
1 to 255
Number of seconds until a timeout occurs to send
or test APDU's (Application Protocol Data Units)
(default = 15)
T2 timeout
1 to 255
Number of seconds until timeout for non-data
acknowledgement (t2 < t1) (default=10)
T3 timeout
1 to 300
Timeout for test frame on idle state in seconds
(default=20)
k (maximum queue)
1 to 12
Maximum number of messages to hold in queue
w (latest ack threshold)
1 to 8
Threshold value when to send ack. This
parameter should be less than or equal to two-
thirds of k.
Originator address for
COT
0 to 255
Originator address in the COT (Cause of
Transmission) to use in all messages from the
client
Response Timeout
500 to 2^32-1
This parameter sets the maximum number of
milliseconds to wait for a confirmation from the
controlled station to a request from this module to
application level messages.
ProSoft Technology, Inc.
Page 63 of 136
March 4, 2013