ProSoft Technology PTQ-104C User Manual
Page 65
49TPTQ-104C ♦ 48TQuantum Platform
Module Configuration
47TIEC 60870-5-104 Client
12TUser Manual
EOI General Int
Y or N
This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command after this module receives
an EOI message from the controlled unit.
Use Time Tag
Commands
Y or N
This parameter specifies if a time tag field is to be
included with commands. This is as specified in
the IEC-870-5-104 specification and should only
be utilized if the controlled device supports these
new data types. If the parameter is set to Y, a time
tag will be added to all commands. If the
parameter is set to N, the normal IEC-870-5-101
data type messages will be utilized
5.6.3 [IEC-104 Client/Session x > IEC-104 Client x Sector 0] section
This section defines the Data Type distribution of the module database for Client
x Sector 0.
Item
Range
Description
Data Type
ASDU type code in message
Point Index
0 to 65535
Value for the Information Object Address (IOA)
Database Address
0 to 64000
Database address in the module associated to
this point according to ASDU type:
Single-point: bit-addressing
Double-point: bit-addressing
Step-point: byte-addressing
ProSoft Technology, Inc.
Page 65 of 136
March 4, 2013