49TPTQ-104C ♦ 48TQuantum Platform
12TUser Manual
47TIEC 60870-5-104 Client
Item
Range
Description
Data Type
ASDU Type
This parameter is used to set the ASDU data
type to be used with the message. The codes
specified are those defined for the IEC-870-5-
101 protocol. The following is a listing of
command control data types supported in this
module:
Type: 45, 46, 47, 48, 49, 50, 51, 100, 101, 102,
103, 105, 107, 110, 111, 112, 113. (Full
descriptions on page 46)
Point Index
1 to 65535
This parameter is the value for the Information
Object Address (IOA) in the target device
Qualifier
1 to 1023
This parameter is dependent on the Data Type
selected. See below for details.
Qualifier Parameter configuration
The Qualifier Parameter is based on a combination of parameters each with their
own value, based on the Type used in the command. The corresponding
parameters for each Data Type have a numerical code assigned to them. The
Qualifier Parameter value is the sum of these numerical codes.
Data Type
Description
Qualifier Parameter
45
Bit address, Single point command
Single Point Value:
0=Off
1=On
46
Bit address, Double point command
Double Point Value:
0=Not permitted
1=Off
2=On
3=Not Permitted
47
Byte address, Regulating step point
command
Regulating Point Value:
0=Not permitted
1=Next step lower if database point is set to -1
2=Next step high if database point set to +1
3=Not Permitted
The following parameters apply to each Data Type (45, 46, 47)
Qualifier Code
0=No additional definition (slave dependent)
4=Short pulse duration
8=Long pulse duration
12=Persistent output
Select/Execute
0=Direct execution without select
128=Select executed followed by execute
256=Deselect command
Page 70 of 136