ProSoft Technology MVI71-MCM User Manual
Page 86

MVI71-MCM ♦ PLC Platform
Reference
Modbus Communication Module
Page 86 of 111
ProSoft Technology, Inc.
December 28, 2007
Offset Register
Content
Description
7 to 8
7607 to 7608
Run Number
These two registers contain the run number value
for the currently running software.
9 7609
Port 1 Command
List Requests
This field contains the number of requests made
from this port to slave devices on the network.
10
7610
Port 1 Command
List Response
This field contains the number of slave response
messages received on the port.
11 7611
Port 1 Command
List Errors
This field contains the number of command errors
processed on the port. These errors could be due
to a bad response or command.
12
7612
Port 1 Requests
This field contains the total number of messages
sent out of the port.
13 7613
Port 1
Responses
This field contains the total number of messages
received on the port.
14
7614
Port 1 Errors
Sent
This field contains the total number of message
errors sent out of the port.
15 7615
Port 1 Errors
Received
This field contains the total number of message
errors received on the port.
16
7616
Port 2 Command
List Requests
This field contains the number of requests made
from this port to slave devices on the network.
17 7617
Port 2 Command
List Response
This field contains the number of slave response
messages received on the port.
18
7618
Port 2 Command
List Errors
This field contains the number of command errors
processed on the port. These errors could be due
to a bad response or command.
19
7619
Port 2 Requests
This field contains the total number of messages
sent out the port.
20
7620
Port 2
Responses
This field contains the total number of messages
received on the port.
21 7621
Port 2 Errors
Sent
This field contains the total number of message
errors sent out of the port.
22
7622
Port 2 Errors
Received
This field contains the total number of message
errors received on the port.
23 7623
Read Block
Count
This field contains the total number of read blocks
transferred from the module to the processor.
24
7624
Write Block
Count
This field contains the total number of write blocks
transferred from the processor to the module.
25 7625
Parse Block
Count
This field contains the total number of blocks
successfully parsed that were received from the
processor.
26
7626
Command Event
Block Count
This field contains the total number of command
event blocks received from the processor.
27 7627
Command Block
Count
This field contains the total number of command
blocks received from the processor.
28
7628
Error Block
Count
This field contains the total number of block errors
recognized by the module.
29 7629
Port 1 Current
Error
For a slave port, this field contains the value of the
current error code returned. For a master port, this
field contains the index of the currently executing
command.