Ladder logic can be written to override the value in the slave status table. It can
disable (state value of 3) by sending a special block of data from the processor to
the slave. Port 1 slaves are disabled using block 3000, and Port 2 slaves are
disabled using block 3100. Each block contains the slave node addresses to
disable. The structure of the block is displayed in the following table:
Offset Description
Length
0
3000 or 3100
1
1
Number of Slaves in Block
1
2 to 61
Slave indexes
60
62 to 63
Spare
2
The module will respond with a block with the same identification code received
and indicate the number of slaves acted on with the block. The format of this
response block is displayed in the following table:
Offset Description
Length
0
3000 or 3100
1
1
Write Block ID
1
2
Number of slaves processed
1
3 to 63
Spare
61
Ladder logic can be written to override the value in the slave status table to
enable the slave (state value of 1) by sending a special block. Port 1 slaves are
enabled using block 3001, and Port 2 slaves are enabled using block 3101. Each
block contains the slave node addresses to enable. The following table describes
the format for this block.
Offset Description
Length
0
3001 or 3101
1
1
Number of Slaves in Block
1
2 to 61
Slave indexes
60
62 to 63
Spare
2
The module will respond with a block with the same identification code received
and indicate the number of slaves acted on with the block. The format of this
response block is displayed in the following table:
Offset Description
Length
0 Reserved
1
1
Write Block ID
1
2
Number of slaves processed
1
3 to 63
Spare
61