beautypg.com

Using the configuration/debug port – ProSoft Technology MVI71-MCM User Manual

Page 37

background image

Diagnostics and Troubleshooting

MVI71-MCM ♦ PLC Platform

Modbus Communication Module

ProSoft Technology, Inc.

Page 37 of 111

December 28, 2007

DOS

ProComm, as well as several other terminal emulation programs

Windows 3.1

Terminal

Windows 95/98

HyperTerminal

Windows NT/2000/XP

HyperTerminal

4.1.4 Using the Configuration/Debug Port

To connect to the module's Configuration/Debug port:

1

Connect your computer to the module's port using a null modem cable.

2

Start the communication program on your computer and configure the
communication parameters with the following settings:

Baud Rate

57,600

Parity None
Data Bits

8

Stop Bits

1

Software Handshaking

None

3

Open the connection. When you are connected, press the [?] key on your
keyboard. If the system is set up properly, you will see a menu with the
module name followed by a list of letters and the commands associated with
them.

If there is no response from the module, follow these steps:

1

Verify that the null modem cable is connected properly between your
computer's serial port and the module. A regular serial cable will not work.

2

Verify that RSLinx is not controlling the COM port. Refer to Disabling the
RSLinx Driver for the Com Port on the PC (page 79).

3

Verify that your communication software is using the correct settings for baud
rate, parity and handshaking.

4

On computers with more than one serial port, verify that your communication
program is connected to the same port that is connected to the module.

If you are still not able to establish a connection, you can contact ProSoft
Technology Technical Support for further assistance.