5.4

MVI71-MCM Database Definition

This section contains a listing of the internal database of the MVI71-MCM
module. This information can be used to interface other devices to the data
contained in the module.

Register Range

Modbus Low

Modbus High

Content

Size

0 to 4999

40001

45000

User Data

5000

5000 to 5006

45001

45007

Backplane Configuration

10

5010 to 5039

45011

45040

Port 1 Setup

30

5040 to 5069

45041

45070

Port 2 Setup

30

5200 to 6199

45901

46900

Port 1 Commands

1000

6400 to 7399

46401

47400

Port 2 Commands

1000

7600 to 7632

47601

47633

Misc. Status Data

33

7800 to 7999

47801

4800

Command Control

200

The User Data area holds data collected from other nodes on the network
(master read commands) or data received from the processor (write blocks).

Additionally, this data area is used as a data source for the processor (read
blocks) or other nodes on the network (write commands).

Detailed definition of the miscellaneous status data area can be found in MVI71-
MCM Status Data Definition (page 85).

Definition of the configuration data areas can be found in the data definition
section of this document and in MVI71-MCM Configuration Data Definition (page
87).

MVI71-MCM Command Error Codes (page 94) contains a discussion of the
command control section of the database.

Configuration Error Codes (page 95) contains a table of Configuration Error
Codes.

5.5

MVI71-MCM Status Data Definition

This section contains a description of the data contained in the status data block.
This data is transferred from the module to the processor either through a BTR
block -1 (block transfer interface) or directly into the configuration file (side-
connect interface).

Offset Register

Content

Description

0

7600

Program Scan
Count

This value is incremented each time a complete
program cycle occurs in the module.

1 to 2

7601 to 7602

Product Code

These two registers contain the product code of
"DFCM"

3 to 4

7603 to 7604

Product Version

These two registers contain the product version
for the current running software.

5 to 6

7605 to 7606

Operating
System

These two registers contain the month and year
values for the program operating system.