Mvi71-mcm database definition, Mvi71-mcm status data definition, Mvi71-mcm – ProSoft Technology MVI71-MCM User Manual
Page 85: Database definition, Status, Data definition

Reference MVI71-MCM
♦ PLC Platform
Modbus Communication Module
ProSoft Technology, Inc.
Page 85 of 111
December 28, 2007
5.4
MVI71-MCM Database Definition
This section contains a listing of the internal database of the MVI71-MCM
module. This information can be used to interface other devices to the data
contained in the module.
Register Range
Modbus Low
Modbus High
Content
Size
0 to 4999
40001
45000
User Data
5000
5000 to 5006
45001
45007
Backplane Configuration
10
5010 to 5039
45011
45040
Port 1 Setup
30
5040 to 5069
45041
45070
Port 2 Setup
30
5200 to 6199
45901
46900
Port 1 Commands
1000
6400 to 7399
46401
47400
Port 2 Commands
1000
7600 to 7632
47601
47633
Misc. Status Data
33
7800 to 7999
47801
4800
Command Control
200
The User Data area holds data collected from other nodes on the network
(master read commands) or data received from the processor (write blocks).
Additionally, this data area is used as a data source for the processor (read
blocks) or other nodes on the network (write commands).
Detailed definition of the miscellaneous status data area can be found in MVI71-
MCM Status Data Definition (page 85).
Definition of the configuration data areas can be found in the data definition
section of this document and in MVI71-MCM Configuration Data Definition (page
87).
MVI71-MCM Command Error Codes (page 94) contains a discussion of the
command control section of the database.
Configuration Error Codes (page 95) contains a table of Configuration Error
Codes.
5.5
MVI71-MCM Status Data Definition
This section contains a description of the data contained in the status data block.
This data is transferred from the module to the processor either through a BTR
block -1 (block transfer interface) or directly into the configuration file (side-
connect interface).
Offset Register
Content
Description
0
7600
Program Scan
Count
This value is incremented each time a complete
program cycle occurs in the module.
1 to 2
7601 to 7602
Product Code
These two registers contain the product code of
"DFCM"
3 to 4
7603 to 7604
Product Version
These two registers contain the product version
for the current running software.
5 to 6
7605 to 7606
Operating
System
These two registers contain the month and year
values for the program operating system.