Diagnostics and Troubleshooting

MVI56-S3964RT ♦ TControlLogix PlatformT

TSiemens 3964R ProtocolT

ProSoft Technology, Inc.

Page 47 of 78

Viewing Configuration Information

Press [C] to view configuration information for the selected port, protocol, driver
or device.

Opening the Serial Port Menu

Press [S] to open the Serial Port menu. Use this command to view and change
additional serial port driver settings.

Viewing Error and Status Data

Press [E] to display the error/status data for the module.

4.2

LED Status Indicators

The LEDs indicate the module's operating status as follows:

ProSoft
Module

Color Status Indication

On

Data is being transferred between the module and a
remote terminal using the Configuration/Debug port.

CFG Green

Off

No data is being transferred on the Configuration/Debug
port.

On

Data being transferred between master and port 1.

P1 Green

Off No

data

On

Data being transferred between master and port 2.

P2 Green

Off No

data

Off

The MVI56-3964R is working normally.

APP Status

Amber

On

The MVI56-3964R module program has recognized a
communication error.

On

The LED is on when the module is performing a write
operation on the backplane.

BP ACT

Amber

Off

The LED is off when the module is performing a read
operation on the backplane. Under normal operation, the
LED should blink rapidly on and off.

Off

The card is not receiving any power and is not securely
plugged into the rack.

Green

The module is operating normally.

OK Red/

Green

Red

The program has detected an error or is being configured.
If the LED remains red for over 10 seconds, the program
has probably halted. Remove the card from the rack and
re-insert the card to restart the module's program.

Off

The battery voltage is OK and functioning.

BAT Red

On

The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for
24 hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.

If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this
indicates a serious problem with the module. Call ProSoft Technology support to
arrange for repairs.