beautypg.com

Setting jumpers, Install the module in the rack – ProSoft Technology MVI56-S3964R User Manual

Page 12

background image

MVI56-S3964RT ♦ TControlLogix PlatformT

Start Here

TSiemens 3964R ProtocolT

Page 12 of 78

ProSoft Technology, Inc.

1.4 Setting

Jumpers

If you use an interface other than RS-232 (default), you must change the jumper
configuration to match the interface. There are three jumpers located at the
bottom of the module.

The following illustration shows the MVI56-S3964R jumper configuration:

1

Set the PRT 2 (for application port 1) and PRT 3 (for application port 2)
jumpers for RS232, RS422 or RS485 to match the wiring needed for your
application. The default jumper setting for both application ports is RS-232.

2

The Setup Jumper acts as "write protection" for the module's flash memory.
In "write protected" mode, the Setup pins are not connected, and the
module's firmware cannot be overwritten. Do not jumper the Setup pins
together unless you are directed to do so by ProSoft Technical Support.

1.5

Install the Module in the Rack

If you have not already installed and configured your ControlLogix processor and
power supply, please do so before installing the MVI56-S3964R module. Refer to
your Rockwell Automation product documentation for installation instructions.

Warning: You must follow all safety instructions when installing this or any other electronic
devices. Failure to follow safety procedures could result in damage to hardware or data, or even
serious injury or death to personnel. Refer to the documentation for each device you plan to
connect to verify that suitable safety procedures are in place before installing or servicing the
device.

April 17, 2008

This manual is related to the following products: