MVI69-S3964R ♦ CompactLogix or MicroLogix Platform

Reference

Siemens 3964R Protocol

Page 68 of 80

ProSoft Technology, Inc.

October 31, 2008

5.3.2 RS-232

When the RS-232 interface is selected, the use of hardware handshaking
(control and monitoring of modem signal lines) is user definable. If no hardware
handshaking will be used, the cable to connect to the port is as shown below:

5.3.3 RS-232

Cable

The assignment of the RS-232 connection cable between PRT1/2 (9 pole) and
CP-544 (25 pole) is as follows:

PRT1/2 Pin

Description

CP 544 Pin

Description

2 RxD

2

TxD

3 TxD

3

RxD

5 Gnd

7

Gnd

Important: The other pins of the RS-232 must not be used.

5.3.4 RS-422

RS-422 Tip

If communication in the RS-422 mode does not work at first, despite all attempts,
try switching termination polarities. Some manufacturers interpret +/- and A/B
polarities differently.