2.2 [Module]

This section defines the configuration for the Module level data.

2.2.1 Module

Name

0 to 80 characters

This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the
configuration file.

2.3 [Backplane

69]

[Backplane 69]

Block Transfer Size : 60 #Number of words in block (must be set to 60)

Status Interval : 0 #Minimum interval (ms) between status blocks

#(0 = disable)

2.3.1 Block Transfer Size

60

This read-only parameter specifies the number of words in each block transferred
between the module and processor. This value is fixed at 60 words.

2.3.2 Status

Interval

Minimum interval (ms) between status blocks (0 = disable)

2.4

[3964R Port x]

This section is used to define the port 1 configuration for the 3964R device

[3964R Port 1]

Enable : Yes #No=Port Disabled,Yes=Port Enabled

Baud Rate : 9600 #Baud rate for port (300, 600, 1200, 2400, 4800,

#9600, 19200, 38400, 57600, 115)

Parity : Even #N=None,O=Odd,E=Even

Data Bits : 8 #7 or 8 data bits for messages

Stop Bits : 1 #1 or 2 stop bits for messages

RTS On : 0 #Delay after RTS set before message sent (mSec)

RTS Off : 0 #Delay after message before RTS dropped (mSec)

Use CTS Line : No #Monitor CTS modem line (Y/N)

Swap : 0 #0=No Data Byte Swapping, 1=Data Byte Swapping

Priority : 1 #0=High Priority, 1=Low Priority

Protocol : 0 #0=3964 RK512, 1=3964

ACK Delay : 1000 #Number of mSec to wait for ACK (Default 1000ms)

Setup Attempts : 1 #Number of times to try to connect to CP (Default 6)

Transmit Attempts : 1 #Number of times to try to transmit to CP (Default 6)