beautypg.com

ProSoft Technology MVI69-S3964R User Manual

Page 63

background image

Reference MVI69-S3964R

♦ CompactLogix or MicroLogix Platform

Siemens 3964R Protocol

ProSoft Technology, Inc.

Page 63 of 80

October 31, 2008

The meaning of the entries and possible values are described below.

Job Identifier

The job identifiers are defined as follows:

Send jobs to a CP:

Job:

Identifier:

3964R with RK512: DB-SEND to CP

0041hex

3964R with RK512: DB-FETCH to CP

0045hex

The MVI69-S3964R receives jobs from a CP automatically without extra
parameterization. To differentiate the header data the MVI69-S3964R adds a
header to the user data received and transfers it to the CompactLogix or
MicroLogix processor.

Receive jobs from a CP

Job:

Identifier:

3964R with RK512: DB-SEND from CP

1141hex

3964R with RK512: DB-FETCH from CP

1145hex

Data Block (DB)

Number of the data block. This data block must exist in the communication
partner (3964R with RK512 only, otherwise to be set to "0").

Data Word (DW)

Number of the data word in the selected data block. The selected data block
must contain this number (3964R with RK512 only, otherwise to be set to "0").

Number of Data Words/Data Bytes

Dependent on the type of communication mode used on port 1/2 of the module,
this value will be interpreted as number of data words. This value defines
whether a job will be carried out with or without subsequent telegram. For jobs
without subsequent telegram the value will be 1 ... 64 words (1 … 128 bytes),
and for jobs with subsequent telegram(s) it will be 65 ... 256 words (129 … 512
bytes).

Coordination Byte 9/10

3964R with RK512 send jobs offer the possibility of entering so called
coordination bytes (byte 9 and 10 in the RK512 telegram header). Otherwise to
be set to "0".

Data Type

The send message can request a data type of Data Words (44h) or Marker
(4Dh). If the value is 0 (zero), then data words is used.

This manual is related to the following products: