MVI69-S3964R ♦ CompactLogix or MicroLogix Platform

Configuring the MVI69-S3964R Module

Siemens 3964R Protocol

Page 28 of 80

ProSoft Technology, Inc.

October 31, 2008

2.4.8 Use CTS Line

Yes or No

This parameter specifies if the CTS modem control line is to be used. If the
parameter is set to No, the CTS line will not be monitored. If the parameter is set
to Yes, the CTS line will be monitored and must be high before the module will
send data. Normally, this parameter is required when half-duplex modems are
used for communication (2-wire).

2.4.9 Swap

0 or 1

This parameter specifies whether bytes should be swapped. 0 = No data byte
swapping, 1 = Data byte swapping.

2.4.10 Priority

0 or 1

This parameter specifies whether the data is high priority or low priority. 0 = High
priority, 1 = Low Priority.

2.4.11 Protocol

0 or 1

0=3964 RK512, 1=3964

2.4.12 ACK Delay

Number of milliseconds to wait for ACK. The default is 1000 ms.

2.4.13 Setup Attempts

Number of times to try to connect to CP (Default 6)

2.4.14 Transmit Attempts

Number of times to try to transmit to CP (Default 6)