ProSoft Technology MVI69-S3964R User Manual

Page 27

background image

Configuring the MVI69-S3964R Module

MVI69-S3964R ♦ CompactLogix or MicroLogix Platform

Siemens 3964R Protocol

ProSoft Technology, Inc.

Page 27 of 80

October 31, 2008

2.4.1 Enable

Yes or No

This parameter specifies whether to enable or disable the port. No = Port
Disabled, Yes = Port Enabled.

2.4.2 Baud

Rate

300 to 115200

This parameter specifies the baud rate to be used on the port. Valid values are
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200.

2.4.3 Parity

None, Odd, Even

Parity is a simple error checking algorithm used in serial communication. This
parameter specifies the type of parity checking to use.

All devices communicating through this port must use the same parity setting.

2.4.4 Data

Bits

7 or 8

This parameter sets the number of data bits for each word used by the protocol.
All devices communicating through this port must use the same number of data
bits.

2.4.5 Stop

Bits

1 or 2

Stop bits signal the end of a character in the data stream. For most applications,
use one stop bit. For slower devices that require more time to resynchronize, use
two stop bits.

All devices communicating through this port must use the same number of stop
bits.

2.4.6 RTS

On

0 to 65535 milliseconds

This parameter sets the number of milliseconds to delay after RTS is asserted
before the data will be transmitted.

2.4.7 RTS

Off

0 to 65535 milliseconds

This parameter sets the number of milliseconds to delay after the last byte of
data is sent before the RTS modem signal will be set low.