8. Applying power - Adjustments
Important remarks:
A. If all the previous steps were accomplished you may now disconnect the motor
leads, turn the power on and continue with the following adjustments.
Step 1 - Applying Power
Apply power and check for LED Vs of the DCB that should be "ON", indicating
that the system supplies are present. The display should read: "F-OK". If you
get another message, refer to the following table to find the cause of the
problem. Turn the power off, clear the cause of the problem and re-power the
unit.
Event
Display
Display
after
Recurring
DIP switch 1 - ON
BAUD
OK
Load is under cont. current limit
CLIM
C-OK
Battery Low
BATT
B-OK
Abort condition (hardware only)
ABRT
A-OK
Amplifier's power stage disabled
*
AMPD
H-OK
-15V out of limits
-15V
F-OK
Under or Over Voltage
VOLT
F-OK
+15V out of limits
+15V
F-OK
Over Temperature
TEMP
F-OK
Commutation problem
CMMT
F-OK
Short condition at the power outputs
SHRT
F-OK
*
The AMPD message appears in two cases:
1. When MO (Motor Off) command is given.
2. Position error exceeds the allowed value.