beautypg.com

Nstructions izing, Champion cooler, Mastercool coolers are made by the best – Essick Air AS20012 User Manual

Page 4

background image

MASTERCOOL COOLERS ARE MADE BY THE

BEST:

CHAMPION COOLER

One of the largest manufacturers of evaporative coolers, Champion
Cooler has produced evaporative coolers that deliver high
performance results and long-lasting durability for over 40 years.
Champion’s engineering, design, and production efforts are directed
at the continued manufacture of products that deliver maximum
performance with minimum maintenance.

The performance or Sensible Heat Capacity of any evaporative cooler is
a function of both the CFM and the efficiency, which should be considered
as part of the sizing process. To help ensure proper sizing of a MasterCool,
use the Index on the following page to locate Performance Data and Sizing
Tables for a specific MasterCool model. Follow the procedure below to
determine the cooler size.

1.

Determine design conditions.

Outside Dry-Bulb

Outside Wet-Bulb

Inside Dry-Bulb (TI)

2.

Determine the design Sensible

Heat Load (Btuh).

3.

Determine the cooler leaving air

temperature (LAT) from the tables.

EXAMPLE

Outside Dry-Bulb = 105

Outside Wet-Bulb = 65

Inside Dry-Bulb = 80

Determine the number of AD100 MasterCool coolers with 2 horsepower

motors required to cool 125,000 Btuh heat load. Assume .5" (water) external
static pressure.

Using the Sizing Tables, the following information should be calculated:

LAT = 72
CFM = 7368
SHC = 1.08(80-72)7368 = 63,660 Btuh
Number of Coolers = 125,000/63,660 = 2

4.

Determine CFM from the

performance tables.

5.

Calculate Sensible Heat

Capacity of cooler using:
SHC =1.08(TI-LAT)CFM

6.

Determine the number of

coolers by dividing the
Sensible Heat Load by the
Sensible Heat Capacity.

NSTRUCTIONS

IZING

This manual is related to the following products: