RA 19-4B 011409

2-11

2.4.2.3.1 PARALLEL CONFIGURATION USING DIP SWITCHES TO CONNECT SENSE LINES IN

PARALLEL AND EXTERNAL WIRES TO CONFIGURE LOCAL SENSING

Figure 2-6 is a simplified diagram of a typical parallel configuration using local sensing via exter-
nal wires to connect V(+) to S(+), V(–) to S(–) and DIP switch settings to connect the sense
leads in parallel. This configuration requires the following:

1. For each supply in parallel set DIP switch positions 1 and 2 to OFF (open) (see Figure 2-1).

2. For each DIP switch between parallel-connected slots (C4 and F8), set DIP switch positions

3 and 4 to ON (closed) to connect sense leads in parallel (see Figure 2-1).

3. For each DIP switch between parallel-connected slots configure position 5 to connect the

current share bus by referring to PAR. 2.4.2.2.

4. Configure Positions 6, 7, and 8 (alarms) of each DIP switch per PAR. 2.4.4.

5. Connect wire between I/O mating connector pin Sense (+) and corresponding power supply

V(+) terminal at DC OUTPUT terminal block.

6. Connect wire between I/O mating connector pin Sense (–) and corresponding power supply

V(–) terminal at DC OUTPUT terminal block.

FIGURE 2-6. TYPICAL PARALLEL CONNECTIONS USING EXTERNAL WIRES FOR

LOCAL SENSING AND DIP SWITCHES TO PARALLEL SENSE WIRES