2-4

RA 19-4B 011409

2.4.1

INDEPENDENT OPERATION

The rack adapter is preconfigured at the factory for independent operation of all slots. DIP
switch positions 3, 4 and 5 associated with each slot must be set to OFF (open) for each power
supply to be operated independently.

NOTE: Either local or remote sensing must be connected for the HSF power supplies to

work properly.

The rack adapter is shipped from the factory with each power supply position configured for
local sensing (see Figure 2-2). Sensing for each slot can be configured independently:

• Local sensing using internal DIP switches

• Local sensing using external jumpers connected to the I/O mating connector or the DC

OUTPUT terminal block.

• Remote sensing