If you choose FIA or VdS, a warning dialog will open, but the choice will be respected after you click OK
on the warning and OK on the original dialog.
If you choose to use equations relying on peak mass flow rate to calculate peak pressure and minimum
leakage required to relieve the peak pressure, entering smaller peak flow rates to override default
values may result in under-estimating minimum venting area required. Such an under-estimation would
lead to over-pressurization if a smaller than necessary vent is installed.
1.8 Change parameters used for running the program – (advanced
operation)
Open FanTestic Integrity if it is not already open.
Click on “Settings” “Advanced - view or change program parameters”