Dipswitch settings standalone mode – RISCO Group SEISMIC Detector RK66S User Manual
Page 9

Seismic Detector
9
EN
DIPSWITCH SETTINGS
STANDALONE MODE
Dipswitch
Description (SW7 OFF)
SW1
SW2
SW3
Used to determine the detector's sensitivity. Sensitivity is a function
of coverage area and surface material.
SW1 SW2 SW3
*OFF *OFF *OFF
ON OFF
OFF
OFF ON OFF
ON
ON OFF
OFF OFF ON
ON OFF
ON
OFF ON
ON
ON
ON
ON
SW4
Used to detect single and extremely brief and intense signals
(including explosions and sledge hammers).
ON: Enable
*OFF: Disable
SW5
SW6
Used to adjust the integration time. In combination with SW1-3 they
establish a threshold value; SW5-6 establishes a cumulative alarm
signal value which, when exceeding the threshold value, triggers
an alarm event.
SW5
SW6 Duration (in sec.)
*OFF *OFF 10
(example:
vending machine)
ON OFF
26
OFF
ON 46
ON
ON
80 (example: bank vault)
SW7
Used to determine Stand Alone or BUS mode (Ensure that the J12
position (as below) matches the SW7 spec. )
ON: BUS
*OFF: Stand Alone
SW8
Used to determine Local or Remote Test
ON: Local. An internal self test is performed every 24 hours from
power-up. Test failure lights up the LEDs (see the Testing the
Detector section) and the LEDs remain lit until the next self test.
*OFF: Remote. A test is activated whenever the TEST input is
connected to GND. If the test passes, the alarm relay opens for
three seconds.
SW9
External test generator
ON: Enable External Test Generator
*OFF: Disable (internal test)
High
Sensitivity
Low
Sensitivity
Low
Sensitivity
High
Sensitivity