Dipswitch settings standalone mode – RISCO Group SEISMIC Detector RK66S User Manual

Page 9

background image

Seismic Detector

9

EN

DIPSWITCH SETTINGS

STANDALONE MODE

Dipswitch

Description (SW7 OFF)

SW1
SW2
SW3

Used to determine the detector's sensitivity. Sensitivity is a function
of coverage area and surface material.

SW1 SW2 SW3

*OFF *OFF *OFF
ON OFF

OFF

OFF ON OFF
ON

ON OFF

OFF OFF ON
ON OFF

ON

OFF ON

ON

ON

ON

ON

SW4

Used to detect single and extremely brief and intense signals
(including explosions and sledge hammers).
ON: Enable
*OFF: Disable

SW5
SW6

Used to adjust the integration time. In combination with SW1-3 they
establish a threshold value; SW5-6 establishes a cumulative alarm
signal value which, when exceeding the threshold value, triggers
an alarm event.

SW5

SW6 Duration (in sec.)

*OFF *OFF 10

(example:

vending machine)

ON OFF

26

OFF

ON 46

ON

ON

80 (example: bank vault)

SW7

Used to determine Stand Alone or BUS mode (Ensure that the J12
position (as below) matches the SW7 spec. )
ON: BUS
*OFF: Stand Alone

SW8

Used to determine Local or Remote Test
ON: Local. An internal self test is performed every 24 hours from
power-up. Test failure lights up the LEDs (see the Testing the
Detector section) and the LEDs remain lit until the next self test.
*OFF: Remote. A test is activated whenever the TEST input is
connected to GND. If the test passes, the alarm relay opens for
three seconds.

SW9

External test generator
ON: Enable External Test Generator
*OFF: Disable (internal test)

High

Sensitivity

Low

Sensitivity

Low

Sensitivity

High

Sensitivity