Relay Outputs

RATINGS

Out1: 250 VAC @ 3 A or 30 VDC @ 3 A (resistive load)
Sub1, Sub2: 250 VAC @ 1 A or 30 VDC @ 1 A (resistive load)

ELECTRICAL NOISE

A suppressor (snubber) should be connected to each

SUPPRESSION

relay contact switching inductive loads, to prevent
disruption to the microprocessor's operation.
Recommended suppressor value: 0.1

μF/470 Ω,

250 VAC (PDX6901)

DEADBAND

For alarm operations, 0-100% of full scale, user selectable

HIGH OR LOW

User may program any relay for high or low trip point

ALARM

DEVIATION ALARM

User may program any relay for a high, low, or range set
point deivation alarm.

RELAY OPERATION

Any relay may be set as an alarm relay or for time
proportional PID control

TIME DELAY

0 to 99 minutes 59 seconds alarm trip delay user
selectable for each alarm. Time proportional PID control
relay activation time delay of 0 to 99 minutes 59 seconds
user selectable.

FAIL-SAFE

Programmable

OPERATION

Independent for each alarm relay

AUTO INITIALIZATION When power is applied to the controller, alarm relays will

reflect the state of the input to the controller except
standby alarms.

Analog Outputs

OUTPUT RANGE

Continuous PID or retransmitting: 4-20 mA (600 W maximum)
Time Proportional PID: 15 VDC pulse (600 W minimum,
current limited at 30 mA) high, less than 0.1 VDC low, cycle
time 1 to 300 seconds, user selectable

SCALING RANGE

Retransmitting 4-20 mA outputs can be scaled for any
display range low and high

ACCURACY

+0.1% of full scale

PD550 Series Nova Programmable Process and Temperature Controller

Instruction Manual

9