This parameter sets the target set point (TSP) for program segment 1. The parameter is
set in the same way for segments 1 to 15 (1.SP1 to 1.SPF).
This parameter determines i f the status of time signal (TS) relay outputs are ON or OFF
for the duration of the program segment. This parameter is set in the same way for
segments 1 to 15 (1.TS1 to 1.TSF).
This parameter sets the running time for the segment. This can be set as OFF or
1 to 99.59 (time unit s et in TMU). In the case of an OFF setting, the program will stop
running after the previous segment. This parameter is set in the same way for segments 1
to 15 (1.TM1 to 1.TMF).
PV
PV
PV
PV
PV
PV
.
.
.
The parameters used to set up program 2 are the same as those used for program 1.
This repeat parameter allows segments set with 1.REN and 1.RST to be repeated during
the program. This setting is the number of times the repeated segments will used in the
program. If set as 0, the repeated segments will repeat infinitely. The default setting it 1.
This parameter establishes the repeat end segment. This is the last segment that will be
repeated. After this segment, the program will cycle back to the segment defined in
1.RST. The repeated segments will appear a number of times as defined in 1.RPT.
This parameter establishes the repeat start segment. This is the first segment that will be
repeated. If the program is set to repeat, after the segment defined in 1.REN the program
will loop back to the segment defined by this parameter.
PV
PV
PV
.
.
.
.
.
.
This parameter sets the target set point (TSP) for program segment 15.
This parameter determines i f the status of time signal (TS) relay outputs are ON or OFF
for the duration of program segment 15.
This parameter sets the running time for segment 15. This can be set as OFF or
1 to 99.59 (time unit s et in TMU). In the case of an OFF setting, the program will stop
running after the previous segment.
Reminder: If a program requires less than the 15 segments possible, set the running time for the segment after
the last segment needed to OFF, and only the segments prior to that segment will be used. For example, to use
only 5 segments, set 1.TM6 to OFF.
?
NOTE
PD550 Series Nova Programmable Process and Temperature Controller
Instruction Manual
28