Precision Digital PD554 User Manual
Page 21
Display
Parameter
Setting Range
Unit
Default
Remark
SUB2
O.ACT
CT
OH
OL
PO
Select Output
HEAT, ALM1, ALM2, ALM3, IS1, IS2, TS,
PEND, RUN
ABS
ALM3
Option
Reverse and
Forward
REV, FWD
ABS
REV
Cycle Time 1
1 to 300 seconds
sec
2 sec
High Limit
of Output
OL + 1 digit to 105.0%
OH>OL
%
100.0%
Low Limit
of Output
-5.0% to OH setting
OH>OL
%
0%
Preset Output
-5.0 to 105.0%
%
0.0%
OUT1
OUT2
OUT3
HEAT
SUB1
Select Output
HEAT, ALM1, ALM2, ALM3, IS1, IS2, TS,
PEND, RUN
ABS
ALM1
Select Output
HEAT, RET
ABS
HEAT
Select Output
HEAT, RET
ABS
RET
Models with
OUT3 Only
Select Output
Type
SSR, SCR
ABS
SSR
When OUT2 or 3
is Set to HEAT
Select Output
HEAT, ALM1, ALM2, ALM3, IS1, IS2, TS,
PEND, RUN
ABS
ALM2
Option
Output Group Parameter Summary
PD550 Series Nova Programmable Process and Temperature Controller
Instruction Manual
21