Universal input type and accuracy – Precision Digital PD554 User Manual
Page 8
K1
-200 to 1370
-300 to 2500
K2
-199.9 to 999.9
0 to 2300
> 0°C : ±0.1% FS ±1 digit
J
-199.9 to 999.9
-300 to 2300
< 0°C : ±0.2% FS ±1 digit
T
-199.9 to 400.0
-300 to 750
B
0 to 1800
32 to 3300
> 400°C : ±0.15% FS ±1 digit
< 400°C : ±5% FS ±1 digit
R
0 to 1700
32 to 3100
±0.15% FS ±1 digit
Thermocouple
S
0 to 1700
32 to 3100
E
-199.9 to 999.9
-300 to 1800
> 0°C : ±0.1% FS ±1 digit
L
-199.9 to 900.0
-300 to 1600
< 0°C : ±0.2% FS ±1 digit
U
-199.9 to 400.0
-300 to 750
N
-200 to 1300
-300 to 2400
> 0°C : ±0.1% FS ±1 digit
< 0°C : ±0.25% FS ±1 digit
W
0 to 2300
32 to 4200
±0.2% FS ±1 digit
Platinel II
0 to 1390
32 to 2500
±0.1% FS ±1 digit
PtA
-199.9 to 850.0
-300 to 1560
±0.1% FS ±1 digit**
PtB
-199.9 to 500.0 -199.9 to 999.9
RTD
PtC
-19.99 to 99.99
-4.0 to 212.0
±0.2% FS ±1 digit
JPtA
-199.9 to 500.0 -199.9 to 999.9
±0.1% FS ±1 digit**
JPtB
-150.0 to 150.0 -199.9 to 300.0
0.4 to 2.0 V
±0.1% FS ±1 digit
1 to 5 V
Process
0 to 10 V
-10 to 20 mV
0 to 100 mV
0.400 to 2.000
1.000 to 5.000
0.00 to 10.00
-10.00 to 20.00
0.0 to 100.0
Temp
Temp
Range (ºC)
Range (ºF)
Accuracy*
Input T
y
p
e
UNIVERSAL INPUT TYPE AND ACCURACY
*Performance within recommended operating conditions (10 to 50°C, 20 to 90% RH)
**For a range scale of 0 to 100°C: +0 .3°C +1 digit, and for a range scale of -100 to 100°C: +0.5°C +1 digit
Process and Temperature Inputs
TEMPERATURE DRIFT Refer to accuracy specifications below
DECIMAL POINT
Up to three decimal places for process inputs:
9.999, 99.99, 999.9, or 9999
REAR JUNCTION
Automatic or off settings for temperature inputs. No user
COMPENSATION
calibration required.
OFFSET ADJUSTMENT Four programmable input bias zones
SENSOR BREAK
Open sensor indicated by PV display flashing S.OPN.
DETECTION
All PID control outputs transmit at the user programmed
percent of full output scale set in parameter Po.
Up or down scale, user selectable; alarm relays will follow
the up or down scale selection.
TRANSMITTER
14 to 18 VDC @ 20 mA; available at terminals OUT2 or
SUPPLY
OUT3, instead of a retransmitting analog output
Display range can be scaled between -1999 and 99
99.
4 to 20 mA Input
To accept a 4 to 20 mA signal, select 0.4 to 2.0 VDC input
and connect a 100
Ω resistor across the input terminals.
PD550 Series Nova Programmable Process and Temperature Controller
Instruction Manual