The parameter to set derivation time for PID control.
Setting ranges of 1.D are OFF or 1 to 6000 seconds.
Its default setting is 30 seconds.

The parameter to set the manual reset in the PID calculation. This setting only functions if
the integral time setting is OFF. This setting always functions for H/C models.

PV

PV

Note: The contents of PID Groups 2, 3, and 4 are the same as PID Group 1.

Display

Parameter

Setting Range

Unit

Default

Remark

n.MR

n.Manual Reset

-5.0 to 105.0%

%

50.0%

For Use

When I=0

ARW

FUZY

PID

n.P

n.I

n.D

Anti-Reset Wind-

Up Select

Auto or 50.0 to 200.0%

%

Auto

Fuzzy

OFF, ON

ABS

OFF

PID Number

MENU (0) or 1, 2, 3 or 4

ABS

MENU

n.Proportional

0.1 to 999.9%

%

10.0%

n.Pro/Time

OFF, 1 to 6000 sec

sec

120 sec

n.Derivation time

OFF, 1 to 6000 sec

sec

30 sec

This parameter establishes the PV range of each of the 3 main PID zones. The range of
PID zone 1 is IN.RL (IN.SL if set for mV or V input) to 1.RP. The range of PID zone 2 is
1.RP to 2.RP. The range of PID zone 3 is 2.RP to IN.RH (IN.SH if set for mV or V input).

This parameter establishes the range of each of the 3 main PID zones. The range of PID
zone 1 is IN.RL (IN.SL if set for mV or V input) to 1.RP. The range of PID zone 2 is 1.RP
to 2.RP. The range of PID zone 3 is 2.RP to IN.RH (IN.SH if set for mV or V input).

This parameter establishes the hysteresis width of the PID zone.

This parameter sets the range of deviation for PID zone 4. When the difference between
the PV and SP is greater th an this deviation range, the controller will utilize PID group 4
for PID settings. While the PV and SP are within this deviation difference, the controller
will utilize whatever zone would normally be used based on the PV value.

PV

PV

PV

PV

1.RP

Reference

Point 1

AEU (0.0%), 1.RP < 2.RP

AEU

AEU

(100.0%)

PID Zone 1

2.RP

Reference

Point 2

1.RP < 2.RP < AEU (100.0%)

AEU

AEU

(100.0%)

PID Zone 2

RHY

Reference

Hysteresis

GEU (0.0 to 10.0%)

GEU

AEU (0.3%) PID Zone 3

RDV

Reference

Deviation

GEU (0.0 to 100.0%)

GEU

AEU (0.0%) PID Zone 4

C.MOD

Control Mode

Differential of Deviation Value (d. dV) or

Process Variable (d. PV)

ABS

d. dV

PD550 Series Nova Programmable Process and Temperature Controller

Instruction Manual

34