background image

To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit breaker
before wiring.

To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit breaker
before wiring.

„ Be sure to connect to correct polarities. Connecting to a wrong polarity may cause a controller malfunction.
„ Use shielded wires for the wiring and connect independently to ground (1 point grounding).

To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit breaker
before wiring.

7.8 Analog Output Connection

!

CAUTION

!

CAUTION

(1) Voltage Pulse Output (SSR) / Current Output (SCR)

!

CAUTION

!

CAUTION

(2) Retransmitting Output (RET)

-

+

OUT2,3 +

NOVA

SHIELD

OUT2,3 -

Control
Device

-

+

RET+

NOVA

SHIELD

RET-

Receiver

(Recorder, etc)

SCR : 4 to 20 mADC, 600

Ω maximum

SSR : 12 VDC min, 600

Ω minimum

4 to 20 mADC, 600

Ω max

or 14-18 VDC @ 20 mA max

PD550 Series Nova Programmable Process and Temperature Controller