beautypg.com

Precision Digital PD554 User Manual

Page 10

background image

Digital Inputs

CONFIGURATION

Two contacts, two operating modes

CONTACTS

Normally open switches (external excitation not required)
or open collector transistor

OPEN CIRCUIT

Approximately 5 VDC

VOLTAGE

LOGIC LEVELS

LO = 0 to 0.8 VDC, HI = 4.7 to 28 VDC

OPERATION

Mode 1: Program hold and step
Mode 2: Program run or reset

Digital Outputs

CONFIGURATION

2 or 4 open collector transistor

OPERATION MODES

Alarms, inner signal PV or SP zones, program segment time
signals, SP status (ramp up/down or soak), program run or
end alerts

TRANSISTOR RATING 24 VDC @ 50 mA

Serial Communications

PROTOCOLS

Modbus (ASCII, RTU), PC software,
SYNC (master SP control)

UNIT ADDRESS

1 to 99 (Max 31 units connected)

BAUD RATE

600, 1200, 2400, 4800, 9600, 19200 bps, user selectable

RESPONSE TIME

0 to 100 ms delay response time
10 ms increments user selectable

DATA

7 or 8 bit user selectable

PARITY

None, even, or odd

Approvals

UL RECOGNIZED

USA and Canada
Process Control Equipment

UL FILE NUMBER

E244207

CE COMPLIANT

PD550 Series Nova Programmable Process and Temperature Controller

Instruction Manual

10

This manual is related to the following products: