5.2 Output Group (G.OUT)

Press SET/ENT key to select input group. (Refer to parameter map in section 3.)

This parameter sets the type of operation for output 1. (OUT1: relay output)
The output can be set to HEAT (PID Control), ALM1, ALM2, ALM3, RUN, IS1, IS2, TS, or
PEND. Its default setting is ALM1. See Notes below.

This parameter establishes the type of operation for output 2. (OUT2: 4-20 mA or voltage
pulse) This output can be set for HEAT (P ID Control) or RET (Retransmitting). Its
default setting is HEAT.

This parameter establishes the type of operation for output 2. (OUT3: 4-20 mA or voltage
pulse) This output can be set for HEAT (P ID control) or RET (retransmitting). Its default
setting is HEAT. Menu appears only on models with the OUT3 output.

This parameter selects the type of output signal for each analog output (OUT2 and OUT3)
when they are set to HEAT. The outputs can be set to SSR (pulse output) or
SCR (4-20 mA). Its default setting is SSR.

PV

PV

PV

PV

This parameter sets the type of operation for auxiliary output 1 (SUB1: relay output)
Output can be set to HEAT, ALM1, ALM2, ALM3, RUN, IS1, IS2, TS, or PEND. Its default
setting is ALM2. Menu appears only on models with the SUB1 output option.

This parameter sets the type of operation for auxiliary output 1 (SUB2: relay output)
Output can be set to HEAT, ALM1, ALM2, ALM3, RUN, IS1, IS2, TS, or PEND. Its default
setting is ALM2. Menu appears only on models with the SUB2 output option.

PV

PV

PV

G.AT

Q G.PID Q PWD Q G.CTL Q G.IS Q G.DO

K

R

G.COM

Q G.RET Q G.ALM Q G.OUT Q G.IN

ST

ST

ST

ST

ST

ST

ST

ST

ST

ST

T

?

NOTE

Output Group Menu Progression Example:
The following settings establish relay out put 1 (OUT1) to trigger based on alarm 1, for analog output 2 (OUT2) to
operate as a heating tem perature controller outputting a voltage pulse, for analog output 3 (OUT 3) to output a
retransmitting 4-20 mA s ignal, and for auxiliary relay outputs SUB1 and SUB2 to trigger with alarm 2 and alarm 3.

PV

SP

PV

SP

PV

SP

PV

SP

PV

SP

PV

SP

oUT1

oUT2

oUT3

HEAT

sUB1

SUB2

alN1

ret

HEAT

aln2

Aln3

ssr

~

~

~

?

NOTE

Output Operation Settings:
HEAT is used to set the outp ut for PID control, as time-proportional control for relay outputs or 4-20 mA or voltage
pulse outputs for analog ou tputs. RUN will set the relays to always on. If set for TS (time signal) the relays will
trigger if the time signal is on for the current program segment (see 1.TS1 under PROG menu). PEND will trigger
relay outputs after the program cycle ends for the time set in PE.TM under G.CTL. For additional information on the
setup of ALM1, ALM2, ALM3 (alarm), IS1, and IS2 (inner signal) refer to G.ALM and G.IS.

PD550 Series Nova Programmable Process and Temperature Controller

Instruction Manual

19