Precision Digital PD554 User Manual
Page 36
PV
Display During Auto-Tuning:
The AT LED on the front panel will blink at a 500 ms time interval.
Changing the Set Point During Auto-Tuning:
If the set point is cha nged during the auto-tuning process, the original set point will be maintained for the
duration of the auto-tuning process. After auto-tuning is complete, the controller will change to the new set
point.
Changing PID Parameters During Auto-Tuning:
The PID values can be changed during the auto-tuning process. After auto-tuning is complete, it will then use
the auto-tune calculat ed PID values. Values changed after auto-tuning will remain set until auto-tuning is run
again.
Auto-Tuning Interruptions or Errors:
The auto-tuning process will end without effect for any of the following reasons:
- Auto-tuning forced to end (Example: Controller power down or stop condition)
- Open sensor (S.OPN) input error detected during the auto-tuning process
- Auto-tuning cycle exceeds 24 hours.
- Control changed to m anual (MAN) operation during auto-tuning.
This parameter effects the proportional value derived by auto-tuning. Reduce the AT-G
gain value and the cycle becomes more rapid, but more unstable. Increasing gain slows
system reaction time, but system stability increases.
Display
Parameter
Setting Range
Unit
Default
Remark
AT
AT-G
Auto Tuning
OFF, ON
ABS
OFF
Auto-Tune
Activation
AT Gain
0.1 to 10.0
ABS
1.0
Gain Value
Fig 10: Auto-Tuning Gain
Gain < 1
Gain = 1
Gain > 1
PID Group Parameter Summary
PD550 Series Nova Programmable Process and Temperature Controller
Instruction Manual
36