Smart wireless thum adapter – Emerson 00825-0100-4075 User Manual
Page 23
Quick Installation Guide
00825-0100-4075, Rev DA
July 2011
Smart Wireless THUM Adapter
23
IECEx Certifications
I7
IECEx Intrinsic Safety
Certificate No.: IECEx BAS 09.0050X
Ex ia IIC T4 (-50 °C
T
amb
70 °C)
IP66
Special conditions for safe use (X)
The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
The enclosure is made of aluminium alloy and given a protective polyurethane paint
finish; however, care should be taken to protect it from impact or abrasion if located in a
zone 0.
N7 IECEx Type n
Certificate No.: IECEx BAS 09.0058
Ex nA IIC T4 (-50 °C
T
amb
70 °C)
Ui = 45 Vdc MAX
IP66
INMETRO Certifications
I2
Intrinsic Safety
BR-Ex ia IIC T4 (-50 °C
T
amb
70 °C) Ga
N2 INMETRO Type ‘n’
BR-Ex nA IIC T4 Gc (-50 °C
T
amb
70 °C)
China (NEPSI) Certifications
I3
China (NEPSI) Intrinsic Safety
Ex ia IIC T4
CCoE Certifications
IW Intrinsic Safety
Ex ia IIC T4
KOSHA Certifications
IP
Intrinsic Safety
Ex ia IIC T4
Table 3. Input Parameters
Loop Power
Ui = 30 V
Ii = 200 mA
Pi = 1.0 W
Ci = 0
Li = 0
4075_QIG_Rev_DA.fm Page 23 Wednesday, July 27, 2011 8:50 AM