beautypg.com

Smart wireless thum adapter, Quick installation guide – Emerson 00825-0100-4075 User Manual

Page 12

background image

Quick Installation Guide

00825-0100-4075, Rev DA

July 2011

Smart Wireless THUM Adapter

12

Figure 14. Direct Mount Wiring Diagram for 4-Wire Active Device

NOTE:
An active loop exists when the wired device is supplying the power to the 4-20 mA
loop. It is important to verify if the wired device is operating in active or passive
mode.

Figure 15. Remote Mount Wiring Diagram for 4-Wire Active Device

Splice Connector

Wired Device

4-20 mA Loop -

4-20 mA Loop +

Ground

THUM Adapter

Green

Yellow

White

Black

Red

Input

Card

Po

w

e

r+

Po

w

e

r-

COMM

+

COMM

-

Load Resistor

250

Remote Mount Housing

4-20 mA Loop -

4-20 mA Loop +

Ground

+ COMM

- COMM

THUM Adapter

Green

Red

Black

White

Yellow

To Wired Device

Shield Wire

Load Resistor

250

Input

Card

4075_QIG_Rev_DA.fm Page 12 Wednesday, July 27, 2011 8:50 AM