Quick Installation Guide

00825-0100-4075, Rev DA

July 2011

Smart Wireless THUM Adapter

10

Figure 10. Direct Mount Wiring Diagram for 4-Wire Passive Device

NOTE:
A passive loop exists when the wired device is not supplying power to the 4–20 mA
loop. It is important to verify if the wired device is operating in active or passive
mode.

Figure 11. Remote Mount Wiring Diagram for 4-Wire Passive Device

Splice Connector

Wired Device

4-20 mA Loop -

4-20 mA Loop +

Ground

THUM Adapter

Green

Red

Black

White

Yellow

Po

w

e

r+

Powe

r-

COMM

+

CO

MM-

Power

+

Supply

-

Load Resistor

250

Remote Mount Housing

4-20 mA Loop -

4-20 mA Loop +

Ground

+ COMM

- COMM

THUM Adapter

Green

Red

Black

White

Yellow

To Wired Device

Shield Wire

Load Resistor

250

+ Power
- Supply